Effect on the thermodynamic performance using N20 and R444B refrigerants instead of R22 in a vapor compression refrigeration system

dc.contributor.authorOruc, Vedat
dc.contributor.authorDevecioglu, Atilla Gencer
dc.date.accessioned2024-04-24T17:18:15Z
dc.date.available2024-04-24T17:18:15Z
dc.date.issued2016
dc.departmentDicle Üniversitesien_US
dc.description.abstractIn this study, the energy and exergy parameters were theoretically investigated for a vapor compression refrigeration system for which N20 and L20 (R444B) refrigerants were used instead of R22. The comparison of the energy parameters was carried out for different evaporation temperatures (-15 degrees C, -10 degrees C, -5 degrees C, 0 degrees C) and condensing temperatures (30 degrees C, 40 degrees C, 50 degrees C) under the same operating conditions. The coefficients of performance (COP) were seen to be in the same order of magnitude for three refrigerants, but the highest COP value was obtained with R22 case. It was seen that the equipments which will use N20 or R444B should have larger condenser surface areas compared to devices operating with R22. It was also determined that the exergetic efficiency of R22 was higher among the investigated refrigerants.en_US
dc.identifier.doi10.17341/gazimmfd.278441
dc.identifier.endpage869en_US
dc.identifier.issn1300-1884
dc.identifier.issn1304-4915
dc.identifier.issue4en_US
dc.identifier.scopus2-s2.0-85015715864
dc.identifier.scopusqualityQ2
dc.identifier.startpage859en_US
dc.identifier.urihttps://doi.org/10.17341/gazimmfd.278441
dc.identifier.urihttps://hdl.handle.net/11468/18694
dc.identifier.volume31en_US
dc.identifier.wosWOS:000392927000005
dc.identifier.wosqualityQ4
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isotren_US
dc.publisherGazi Univ, Fac Engineering Architectureen_US
dc.relation.ispartofJournal of The Faculty of Engineering and Architecture of Gazi University
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectR22en_US
dc.subjectN20en_US
dc.subjectR444ben_US
dc.subjectGlobal Warming Potentialen_US
dc.subjectExergyen_US
dc.titleEffect on the thermodynamic performance using N20 and R444B refrigerants instead of R22 in a vapor compression refrigeration systemen_US