Improvement of energy parameters using R442A and R453A in a refrigeration system operating with R404A

dc.contributor.authorOruc, Vedat
dc.contributor.authorDevecioglu, Atilla G.
dc.contributor.authorEnder, Sertac
dc.date.accessioned2024-04-24T16:10:51Z
dc.date.available2024-04-24T16:10:51Z
dc.date.issued2018
dc.departmentDicle Üniversitesien_US
dc.description.abstractIn this study, R404A having high GWP (global warming potential) was experimentally compared with R442A and R453A refrigerants which have low GWP. The alternatives refrigerants of R442A and R453A were directly tested without performing a constructional modification in the refrigeration system. Three different evaporation temperature (-6, -3 and 0 degrees C) and three condenser temperature (35, 40, 45 degrees C) cases were investigated in the experimental work. Power consumption of compressor was highest for R404A while it was the lowest for R453A at three condenser temperatures. The measurements presented that cooling capacity amounts of R442A and R453A were greater by 1-8% than that of R404A. In comparison with R404A, COP (coefficient of performance) value was better by 5-12% using R442A and it was substantially improved by about 10-14% for the case of R453A refrigerant. The volumetric efficiency values were obtained as the highest for R453A at the covered experimental cases. The mass flow rate and quality of refrigerant at evaporator inlet were also reduced as a result of using considered alternatives refrigerants. (C) 2017 Elsevier Ltd. All rights reserved.en_US
dc.description.sponsorshipDicle University Scientific Research Projects Coordination Unit [MUHENDISLIK 15-001]en_US
dc.description.sponsorshipThe authors are indebted to Dicle University Scientific Research Projects Coordination Unit for the financial support through research project no. MUHENDISLIK 15-001.en_US
dc.identifier.doi10.1016/j.applthermaleng.2017.10.035
dc.identifier.endpage249en_US
dc.identifier.issn1359-4311
dc.identifier.scopus2-s2.0-85030862269
dc.identifier.scopusqualityQ1
dc.identifier.startpage243en_US
dc.identifier.urihttps://doi.org/10.1016/j.applthermaleng.2017.10.035
dc.identifier.urihttps://hdl.handle.net/11468/15153
dc.identifier.volume129en_US
dc.identifier.wosWOS:000419407500024
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoenen_US
dc.publisherPergamon-Elsevier Science Ltden_US
dc.relation.ispartofApplied Thermal Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectDrop-Inen_US
dc.subjectR404aen_US
dc.subjectR442aen_US
dc.subjectR453aen_US
dc.subjectGwpen_US
dc.titleImprovement of energy parameters using R442A and R453A in a refrigeration system operating with R404Aen_US
dc.titleImprovement of energy parameters using R442A and R453A in a refrigeration system operating with R404A
dc.typeArticleen_US