PERFORMANCE ANALYSIS OF COOLING SYSTEM WITH HORIZONTAL TYPE GROUND SOURCE HEAT PUMP FOR DIYARBAKIR CONDITIONS

dc.contributor.authorKoçyiğit, Fatih
dc.date.accessioned2024-04-24T19:11:47Z
dc.date.available2024-04-24T19:11:47Z
dc.date.issued2020
dc.departmentDicle Üniversitesien_US
dc.description.abstractIn this study, the performance of the horizontal type ground source heat pump cooling system in the summer was analyzed for cooling the testing area with a size of 9x8x2.8m in Diyarbakır province with a warm climate. Energy and exergy analysis was applied to the system and system units by examining the results obtained in the summer in the evaluated system. The monthly and seasonal mean values of the data in the summer (01.06.2018 / 30.08.2018 ) were taken for 11 node points determined in the installed system. In the energy analysis performed with the results obtained, it was calculated that the energy loss in the system was 2.499kW and the energy efficiency 76.86%. For the system units, the unit operating with the lowest energy efficiency was determined as the compressor. According to exergy analysis applied to the system, it was calculated that the exergy loss of the system was 2.150 kW and the second law efficiency was 20.70%. The compressor was also determined as the unit with the highest exergy loss in the system. Compressor should be prioritized for improvement studies to be planned according to both energy and exergy analysis results. The COP value of the system was found to be 4.05, and it was determined that the system, the use of which was examined in the summer, could be used for Diyarbakır province.en_US
dc.identifier.doi10.36222/ejt.704301
dc.identifier.endpage130en_US
dc.identifier.issn2536-5010
dc.identifier.issn2536-5134
dc.identifier.issue1en_US
dc.identifier.startpage119en_US
dc.identifier.trdizinid472905
dc.identifier.urihttps://doi.org/10.36222/ejt.704301
dc.identifier.urihttps://search.trdizin.gov.tr/yayin/detay/472905
dc.identifier.urihttps://hdl.handle.net/11468/28200
dc.identifier.volume10en_US
dc.indekslendigikaynakTR-Dizin
dc.language.isoenen_US
dc.relation.ispartofEuropean Journal of Technique
dc.relation.publicationcategoryMakale - Ulusal Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.titlePERFORMANCE ANALYSIS OF COOLING SYSTEM WITH HORIZONTAL TYPE GROUND SOURCE HEAT PUMP FOR DIYARBAKIR CONDITIONSen_US
dc.titlePERFORMANCE ANALYSIS OF COOLING SYSTEM WITH HORIZONTAL TYPE GROUND SOURCE HEAT PUMP FOR DIYARBAKIR CONDITIONS
dc.typeArticleen_US

Dosyalar