Experimental assessment of the retrofit of an internal heat exchanger in refrigeration systems: The effect on energy performance and system operation

Yükleniyor...
Küçük Resim

Tarih

2020

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Pergamon-Elsevier Science LTD

Erişim Hakkı

info:eu-repo/semantics/restrictedAccess

Özet

The aim of this experimental study is to retrofit a refrigeration system with an internal heat exchanger (IHX) and to assess its effect on the energy performance of the system. The separate IHX cases in the investigation are tube-in-tube type and plate type and these are also compared with the system without any IHX. R404A and R442A refrigerants are tested in a single stage vapour compression refrigeration system. In the experimental work evaporation temperatures of −5°C and 0°C are considered while the condenser temperatures are 30°C and 50°C. The results indicated that both utilised types of IHX elements improved the energy performance of the system while the benefit with the tested plate type IHX case was better. Also, the alternative refrigerant R442A can be preferred as a substitute for R404A due to the enhanced energy performance of the system. The thermal effectiveness of IHX devices and the volumetric efficiency of the compressor are considered as well for the evaporation and condenser temperatures covered.

Açıklama

Anahtar Kelimeler

Retrofit, Tube-in-tube IHX, Plate IHX, R404A, R442A

Kaynak

Applied Thermal Engineering

WoS Q Değeri

Q1

Scopus Q Değeri

Q1

Cilt

180

Sayı

Künye

Oruç, V. ve Devecioğlu, A.G. (2020). Experimental assessment of the retrofit of an internal heat exchanger in refrigeration systems: The effect on energy performance and system operation. Applied Thermal Engineering, 180, 115843