Seasonal performance assessment of refrigerants with low GWP as substitutes for R410A in heat pump air conditioning devices
[ X ]
Tarih
2017
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Pergamon-Elsevier Science Ltd
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
In this study, the effect of the utilization of refrigerants with a low Global Warming Potential (GWP) instead of R410A in air conditioners on seasonal efficiency was evaluated theoretically. In the study, four different alternative refrigerants were used namely, R446A, R447A, R452B and R454B. The GWP values of all of the studied refrigerants were lower than 750. The calculations were made according to the EN 14825 standard. Average seasonal conditions were applied for heating. The results showed that R446A had the lowest heating capacity and electric consumption. R446A required electric energy consumption for extra heating due to its low heating capacity and therefore it had the lowest seasonal coefficient of performance (SCOP) value. The seasonal energy efficiency ratio (SEER) values of the refrigerants were very close to each other and their average was 6.56. R452B had the most suitable with 3.92 SCOP value among the alternative refrigerants. (C) 2017 Elsevier Ltd. All rights reserved.
Açıklama
Anahtar Kelimeler
Seer, Scop, R410a, Gwp
Kaynak
Applied Thermal Engineering
WoS Q Değeri
Q1
Scopus Q Değeri
Q1
Cilt
125