Retrofitting of R-22 Air-conditioning system with R1234ze(E)
[ X ]
Tarih
2020
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Springer International Publishing Ag
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
In this study, the effect on energy parameters and total equivalent warming impact (TEWI) using R1234ze(E) as a substitute for R22 in an air-conditioning device was investigated. The R22 system was retrofitted with R1234ze(E) changing compressor oil. The experimental data was obtained for three different ambient temperatures (30, 35 and 40 degrees C). It was seen that the power consumption of R1234ze(E) was smaller than that of R22 about by 41%. Although the cooling capacity of R1234ze(E) was 50% lower, its coefficient of performance (COP) was reduced only by 5% compared to R22. Furthermore, refrigerant charging amount of R1234ze(E) was smaller by 16% than R22. The results indicated that TEWI value of R1234ze(E) was lower than that of R22 by 65% due to small GWP (global warming potential) value and proper COP of the alternative refrigerant tested in the study. Hence, it can be expressed that R1234ze(E) can be used in air-conditioners of small capacity as an alternative to R22.
Açıklama
7th Global Conference on Global Warming (GCGW) -- JUN 24-28, 2018 -- Izmir, TURKEY
Anahtar Kelimeler
Gwp, Tewi, Retrofitting, R22, R1234ze(E)
Kaynak
Environmentally-Benign Energy Solutions
WoS Q Değeri
N/A
Scopus Q Değeri
Q3
Cilt
Sayı
Künye
Devecioğlu, A.G. ve Oruç, V. (2020). Retrofitting of R-22 air-conditioning system with R1234ze(E). Green Energy and Technology, 7th Global Conference on Global Warming, GCGW 2018Izmir24 June 2019 through 28 June 2019, 87–96.