Improvement on the energy performance of a refrigeration system adapting a plate-type heat exchanger and low-GWP refrigerants as alternatives to R134a

[ X ]

Tarih

2018

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Pergamon-Elsevier Science Ltd

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

This study is directed to propose a method for enhancing the energy parameters of the refrigeration systems operating with R134a which generally presents low performance of the units. Hence, R134a was experimentally compared with HFO-based refrigerants of R1234yf and R1234ze(E) having low-GWP. Additionally, plate-type liquid to suction heat exchanger (LSHX) was utilized in order to determine its effect on the system's energy performances. The evaporation temperatures were -9, -4.5 and 0 degrees C while the condenser temperatures were 40, 45, and 50 degrees C in the experimental work. The cooling capacity and power consumption of R1234ze(E) were noticed lower, however its COP was higher compared to R1234yf. It was also figured out that COP of the system with LSHX using R1234ze(E) was better about by 3% than that without LSHX which operated with R134a. The results of the present study indicated that the presence of LSHX caused improved COP and lower power consumption of the refrigeration system. (C) 2018 Elsevier Ltd. All rights reserved.