Özet
The aim of this study is to investigate the possibilities for satisfying F-Gas regulation of European Union (EU) using R455A with low-global warming potential (GWP) in refrigeration systems. Hence an experimental work was conducted for energy analysis of a refrigeration system constructed to operate with R404A. The studied evaporation temperatures were -5 and + 5 degrees C while the condenser temperatures were 35 and 55 degrees C. It was determined that COP values of R455A were higher about by 13.7% compared to R404A. The results of the present investigation point out that R455A is suitable to use in refrigeration systems due to better energy performance. It is possible to use R455A in refrigeration systems after 2022 with respect to the EU regulation 517/2014. (C) 2021 Elsevier Ltd. All rights reserved. Selection and peer-review under responsibility of the scientific committee of the International Conference on Smart and Sustainable Developments in Materials, Manufacturing and Energy Engineering.
Açıklama
3rd International Conference on Smart and Sustainable Developments in Materials, Manufacturing and Energy Engineering (SME)
WOS:000782656100002
WOS:000782656100002
Anahtar Kelimeler
R455A, Low-GWP, EU 517/2014, F-Gas regulation
Kaynak
Materials Today: Proceedings
WoS Q Değeri
N/A
Scopus Q Değeri
Q2
Cilt
52
Sayı
Part 3
Künye
Devecioğlu, A.G. ve Oruç, V. (2022). On the satisfaction of EU F-Gas regulation using R455A as an alternative to R404A in refrigeration systems. Materials Today: Proceedings, 52(Part 3), 1865-1869.